- Thanks to 2-phase control, not only is the current kept at minimum values in all three phases throughout the entire starting time, but disturbing direct current components are also eliminated. This not only enables the 2-phase starting of motors up to 55 kW (at 400 V) but also avoids the current and torque peaks which occur e.g. with star-delta (wye-delta) starters.
- The SIRIUS 3RW40 soft starters are suitable for the starting of explosion-proof motors with “increased safety” type of protection EEx e according to ATEX Directive 94/9/EC.
- This soft starter comes with additional integrated functions such as settable current limiting, motor overload and intrinsic device protection, and optional thermistor motor protection
- This compact soft starter offers many different diagnostics options. Up to four LEDs and relay outputs permit differentiated monitoring and diagnostics of the operating mechanism by indicating the operating state as well as for example mains or phase failure, missing load, non-permissible tripping time/CLASS setting, thermal overloading or device faults.
- Small and compact design
3RW40
The SIRIUS 3RW40 Basic Performance soft starters are suitable for soft starting and stopping of three-phase asynchronous motors.
2-phase control, up to 55 kW (at 400 V)
- Operational voltage: 200 ~ 600VAC
- Operational current at 40 °C: 12,5 ~ 106A
- Rated control supply voltage: 24VDC / 230VAC
- Operating power for three-phase motors at 400V, 40 °C
- Inline circuit: 5,5 ~ 55 kW
- Inside-delta circuit: 7,5 ~ 75 kW
- Minimum load (% of Ie): 20%
- Starting voltage: 40 ~ 100%
- Ramp-up and ramp-down time: 1 ~ 20s
- Maximum starting time: 10s
- Maximum starting current (% of Ie): 300%
- Maximum number of starts per hour: 5/h
- Number of parameter sets: 1
- Number of controlled phases: 2
- Maximum conductor length between soft starter and motor: 300m
- Features:
- Soft starting/ramp-down
- Voltage ramp
- Integral bypass contact system
- Intrinsic device protection
- Motor overload protection
- Thermistor motor protection evaluation
- Remote RESET
- Adjustable current limiting